Unit 2 — Introduction to Refrigerants & Handling Practices
Section 2 — Leak Testing, Evacuation and Charging
2.3 Gases & Liquids for System Pressure Tests
Acceptable test media for primary and secondary systems, volume estimation,
and step-by-step pressure and leak testing procedures.
2.3.1 Gases for Pressure Testing
Only specific gases are acceptable for pressure testing refrigeration and air
conditioning systems. Their use must comply with applicable codes and
manufacturer instructions. Selecting the wrong gas — particularly oxygen or
compressed air in primary circuits — creates serious safety hazards.
🔵
Nitrogen
The most common pressure test gas in field service. Dry and inert — used
alone or mixed with a small percentage of refrigerant for leak detection.
🛡️
Argon
Inert. Sometimes used where welding operations are associated with the
pressure test. Non-reactive and non-flammable.
💨
Carbon Dioxide
Used as a test gas in specific high-pressure systems. Requires
pressure-rated equipment matched to CO₂ service.
🔍
Helium
Used in very low leak rate testing in combination with specialized mass
spectrometer detectors. Not for general field pressure testing.
⚗️
Inert Gases
Non-reactive gases such as nitrogen and argon that do not combust or
react with system materials. The preferred family for primary circuits.
⚠️
Air — Secondary Systems Only
May be used in some secondary systems that do not contain primary
refrigerant. Generally avoided in primary circuits due to moisture and
oxidation issues.
Nitrogen is the standard pressure test gas for refrigeration and air
conditioning systems in field service.
- Dry and inert — introduces no moisture and does not react with refrigerant oils or system materials.
- Used alone for a straight pressure test or mixed with a small percentage of refrigerant to provide a detectable trace for leak detection methods.
- Must always be supplied through a properly rated and adjusted regulator — never connect a nitrogen cylinder directly to a system.
- Available in high-pressure cylinders; verify cylinder contents and pressure before use.
Argon is an inert gas that is non-reactive and non-flammable.
- Sometimes used for pressure testing where welding or TIG/MIG operations are associated with the work, as the same gas supply may be used for both.
- Like all inert gases, can displace oxygen in confined spaces — adequate ventilation is required.
Carbon dioxide is used as a test gas in specific high-pressure system
applications.
- Requires pressure-rated equipment — regulators, gauges, hoses, and fittings must be rated for CO₂ service and the applicable pressures.
- Non-flammable but can cause asphyxiation in high concentrations — ensure adequate ventilation during use.
Helium is used in very low leak rate testing applications where
conventional methods are not sensitive enough.
- Used in combination with mass spectrometer leak detectors for extremely sensitive leak detection.
- Small molecular size allows helium to pass through very small leaks that other gases cannot — making it ideal for precision testing of critical components.
- Not a standard field test gas; more common in factory, laboratory, or specialized industrial applications.
Compressed air must be used with caution and is generally avoided in
primary refrigerant circuits.
- May be used in some secondary systems — such as hydronic loops or glycol circuits — that do not contain primary refrigerant.
- Avoid in primary refrigerant circuits — compressed air introduces moisture and can form explosive mixtures with certain refrigerants under pressure.
- Oxygen must never be used for pressure testing under any circumstances.
2.3.2 Liquids for Pressure Testing Secondary Systems
Secondary systems such as hydronic loops are often hydrostatically tested using
liquids rather than gases. Hydrostatic testing is inherently safer than gas
testing at the same pressure — liquids are nearly incompressible, so a sudden
failure releases far less stored energy than a pressurized gas system.
🌊
Water
Most commonly used for hydrostatic testing at ambient temperatures.
Suitable provided freezing is not a risk during or after the test.
💧
Glycol
Ethylene or propylene glycol mixtures. Used to pressurize and test closed
hydronic loops, especially where freeze protection is required.
🧂
Brine
Salt-water solutions used for testing low-temperature secondary circuits
that operate below water's freezing point.
Water is the most common liquid used for hydrostatic pressure testing
at ambient temperatures.
- Suitable for most secondary system tests provided freezing is not a risk during or after the test procedure.
- After testing, piping must be thoroughly drained and dried — especially before connecting to refrigeration circuits or where freezing temperatures could occur.
- Potable water is preferred to prevent corrosion or biological growth in the piping.
Ethylene or propylene glycol mixed with water in the appropriate
concentration for the design operating temperature.
- Used to pressurize and test closed hydronic loops where the system will ultimately operate with glycol as the secondary coolant.
- Testing with the intended operating fluid avoids later contamination from residual water left after a water-only test.
- Propylene glycol is preferred over ethylene glycol in applications where incidental contact with food or potable water is possible.
Brine solutions — typically calcium chloride or sodium chloride in water —
are used for testing low-temperature secondary circuits.
- Used where the circuit operates below water's freezing point and must remain liquid during and after the test.
- Brines can be corrosive — piping materials, fittings, and seals must be compatible, and corrosion inhibitors may be required.
- Spills must be cleaned up promptly to prevent corrosion of structural components and environmental contamination.
💡
Gas vs. Liquid Testing — Safety Consideration
Hydrostatic (liquid) testing is inherently safer than pneumatic (gas) testing
at the same pressure. Pressurized liquids store very little energy compared to
compressed gases — a pipe failure during hydrostatic testing causes a slow leak
or localized rupture rather than the explosive release that can occur with a
high-pressure gas test. Where codes permit a choice, hydrostatic testing is
preferred for secondary systems.
2.3.3 Calculating Test Gas and Liquid Volume
Before pressure testing, technicians must estimate the volume of gas or liquid
required to achieve the desired test pressure — without overpressurizing equipment
or exhausting the gas supply before reaching the target.
- Estimate system volume from piping dimensions, component sizes (receivers, vessels, coils), and manufacturer data sheets.
- Apply gas laws (Boyle's Law: P₁V₁ = P₂V₂ at constant temperature) to relate initial cylinder pressure and volume to the final test pressure in the system — where accurate calculations are required.
- Increase pressure in controlled steps — never open the regulator to full test pressure immediately. Step up gradually, verifying gauge stability at each intermediate pressure before continuing.
Inputs Needed
- Pipe lengths and internal diameters
- Vessel and receiver volumes
- Component internal volumes (if significant)
- Desired test pressure
- Available cylinder pressure and volume
Key Precautions
- Never exceed the maximum allowable test pressure
- Isolate components not rated for the test pressure
- Remove or bypass pressure relief devices if required by the test procedure
- Monitor continuously — do not leave pressurized systems unattended
- Document final test pressure, duration, and result
2.3.4 Pressure and Leak Testing Procedures
Pressure and leak testing follows a defined sequence to ensure safety,
accuracy, and compliance with applicable codes. The steps below represent
the standard procedure covered in apprenticeship training.
-
Isolate the test section. Close all valves not involved
in the test. Remove, bypass, or protect components not rated for the
test pressure (e.g., pressure switches, relief valves if required by
procedure).
-
Connect the test assembly. Attach a nitrogen cylinder
with a properly adjusted regulator and gauge manifold to the test section.
Verify all connections are tight and hoses are rated for the test pressure.
-
Raise pressure in steps. Pressurize gradually to an
intermediate value — typically 25–50% of the final test pressure. Hold and
verify stability before continuing. Then increase to the final test pressure
as specified by code or the equipment manufacturer.
-
Hold and monitor. Maintain pressure for the required hold
time while monitoring gauges for any pressure drop. A drop indicates a
leak or a problem with the test setup.
-
Locate leaks if present. If a pressure drop is observed,
use approved detection methods — soap solution, electronic detectors,
ultrasonic detection, or fluorescent dyes — to identify and mark leak
locations. Repair leaks and retest.
⚠️
After the Test
Once the pressure test is complete and all leaks have been repaired and
verified, safely vent or recover the test gas as appropriate (recover any
refrigerant-containing mixture; vent inert nitrogen safely away from
ignition sources and confined spaces). Document the test pressure, hold
duration, and pass/fail result before proceeding to evacuation.